Cantidad | Precio en USD |
---|---|
1+ | $161.110 |
Información del producto
Resumen del producto
HGLND-D2-DT is a high performance 3-stage lightning protector provides superior protection of differential or balanced digital or analog lines from transients and surges. The unit will protect two pairs of differential data or analog/control lines. The first stage is comprised of a differential gas discharge tube. Stage two is a pair of current limiting series resistors and the final stage is a low capacitance diode array. The use of three terminal differential gas discharge tubes provides superior common and differential mode protection against conducted transients versus the use of lower cost two terminal tubes. The second stage series resistance limits the power dissipation of the fast diode clamp array in the third stage. This allows time for the slower but higher power gas tubes to flash over. The diode array clamps the leading edge of fast transients to safe levels until the high power gas tubes turn on. Application includes DSL/telephone lines.
- DIN 3 rail mountable
- 3-stage surge protection
- Superior to diode or TVS only based designs
- Failsafe mode of operation, die cast aluminum construction
- Stage 1 withstand voltage is ±230V, stage 2 resistance is 3.3ohm, stage 3 clamping voltage is ±170V
- Maximum ground lug is 10AWG
- Operating temperature range from -40 to +80°C
- Dimensions (WxHxL) is 4.5 x 2.5 x 1.5inch
Especificaciones técnicas
Protección contra Sobrevoltajes
-
-
-
0
To Be Advised
Documentos técnicos (1)
Legislación y medioambiente
RoHS
RoHS
Certificado de conformidad del producto